For industrial and commercial power distribution systems requiring a safe, reliable, and low-maintenance solution, Dry Type Step Down Transformers are the premier choice. These transformers are engineered for efficiency and durability, offering significant advantages over traditional liquid-filled units by eliminating the risks and maintenance associated with insulating oils. Many of our high-performance models utilize advanced Silicon Steel Transformer cores, which are meticulously designed to minimize core losses and enhance overall energy efficiency, leading to lower operational costs over the transformer's lifespan. This specific construction falls under the category of a Dry Type Silicon Steel Transformer, combining the safety of dry-type technology with the superior magnetic properties of grain-oriented silicon steel. A common and critical application in medium-voltage networks is the 11kv 433v distribution transformer, which effectively steps down voltage from an 11kV primary supply to a usable 433V secondary output for facility equipment. As a leading provider of robust Distribution Transformer solutions, we ensure our products meet stringent international standards for performance, safety, and environmental compliance, making them ideal for installations in hospitals, data centers, schools, and manufacturing plants.
Our Dry Type Step Down Transformer is built with longevity and operational stability as core principles. The absence of flammable insulating liquids allows for installation in indoor environments without the need for fireproof vaults or complex containment systems, significantly reducing installation space and cost. The windings are vacuum pressure impregnated (VPI) with high-temperature, Class H or F insulation resins, providing excellent protection against moisture, dust, and corrosive atmospheres. This robust construction ensures reliable performance even in harsh conditions. The completely sealed core and coil assembly prevents contamination and reduces acoustic noise, contributing to a quieter operational profile. Designed for easy integration into modern smart grids, these transformers often come equipped with temperature monitoring systems and optional protective enclosures (IP ratings) to suit specific environmental requirements.
Below are the detailed technical parameters for our standard range of Dry Type Step Down Transformers, highlighting their design flexibility and robust performance characteristics.
| Rated Power (kVA) | Primary Voltage (kV) | Secondary Voltage (V) | No-load Loss (W) | Load Loss at 75°C (W) | Impedance (%) | Sound Level dB(A) |
|---|---|---|---|---|---|---|
| 100 | 11 | 433 | 270 | 1650 | 4.5 | ≤ 55 |
| 250 | 11 | 433 | 460 | 3100 | 5.0 | ≤ 58 |
| 500 | 11 | 433 | 720 | 5200 | 5.5 | ≤ 60 |
| 800 | 11 | 433 | 980 | 7500 | 6.0 | ≤ 62 |
| 1000 | 11 | 433 | 1150 | 9000 | 6.0 | ≤ 63 |